Another Workshop lighting problem

Another Workshop lighting problem

Home Forums General Questions Another Workshop lighting problem

Viewing 21 posts - 1 through 21 (of 21 total)
  • Author
    Posts
  • #376022
    Dave C
    Participant
      @davec87625

      I have 4 twin fluorescent light fittings in my workshop. 5ft and all less than 18 months old and bought new. They are not the kind that require the plug in starters.

      My issue is that 99% of the time they all work fine but occasionally 1 or sometimes 2 of the fittings / lights will not come on. Not always the same light or lights. It can be quite random and infrequent when it happens. They are all wired to one light switch in line from one light to the other ( Series ? )

      If I repeatedly switch the light switch on and off a couple of times this tends to bring them all back on and then the issue may not happen again for a few months ?

      I was considering replacing them for LED's even though the light fittings are relatively new ( 18 months ) Is the issue likely the fittings or another electrical issue and am I likely to get the same problem with LED fittings.

      The light switch is a twin with the other switch controlling the external light which has never given me an issue.

      The light fittings were from 2 separate well known DIY stores.

      Any help appreciated please

      #26238
      Dave C
      Participant
        @davec87625
        #376023
        Tony Pratt 1
        Participant
          @tonypratt1

          I am not an electrician but could it be loose connections/wire[s]?

          Tony

          #376024
          Frances IoM
          Participant
            @francesiom58905

            how cold is the workshop?

            too cold and some tubes will not fire – it is possible that the electronic ballast is ‘too clever’ and having determined that the tube won’t fire has assumed a faulty tube and switched off until restarted by re-application of power.

            #376027
            Dave C
            Participant
              @davec87625

              The workshop is brick and thermollte block construction with cavity wall insulation so never gets too cold to be honest.

              #376031
              Mark Rand
              Participant
                @markrand96270

                Try wiggling the tubes back and fourth a bit in their sockets. Could easily be a poor connection to one of the heaters.

                #376048
                not done it yet
                Participant
                  @notdoneityet

                  Posted by Dave C on 15/10/2018 11:23:36:

                  The workshop is brick and thermollte block construction with cavity wall insulation so never gets too cold to be honest.

                  The workshop is presumably heated continuously? On a thermostat?

                  If not heated, the area will eventually assume external ambient temperature. The insulation simply slows down the heat transfer in or out, so extending the time temperature changes take place (depending on the delta between outside and inside – and assuming no air changes due to draughts).

                  Do you mean one or two fittings (twins) do not illuminate – or one or two tubes?

                  If they are all 230 volt units they will be wired in parallel.

                  I would think it will be temperature which is causing the problem. Is the ‘few months’, without any problem, time of year related?

                  I have two ‘starter’ type flourescents in two adjacent rooms (but no door to separate them. One is over 40 years old and always strikes within about a second and has only had one replacement tube (if at all) in that time, while the other, which is only 25 years old, has gone through several tubes, often fails to strike (particularly when cold) and always takes 2 seconds or more to strike.

                  #376057
                  Speedy Builder5
                  Participant
                    @speedybuilder5

                    Dave C – Who did the wiring. If done by a professional or someone who understands mains wiring and was technically capable they will be in PARALLEL. If they were in series, then each fitting would only get 240/4 = 60 volts each. Probably not even light up at all !

                    How far is the lighting circuit away from the house incoming mains ?

                    Have you checked what sort of voltage you get on the lighting circuit ?

                    BobH

                    #376059
                    pgk pgk
                    Participant
                      @pgkpgk17461

                      Changing to leds doesn't mean you throw the fittings away but you do have to be comfortable with removing the ballasts and rewiring according to the led tube type. I did one of mine about 18mths ago and if memory serves there was enough wire in there after dumping the ballast to make the change-over with the judicious use of one auto bullet crimp connector.

                      pgk

                      #376065
                      Peter Bell
                      Participant
                        @peterbell11509

                        A friend had a a similar problem, ie nothing wrong and new lights and it turned out the electronic ballasts were voltage sensitive and the incoming supply was occasionally too high causing them to shut down at random. He cures it by switching a water heater on when it happens.

                        #376075
                        Dave C
                        Participant
                          @davec87625

                          I may have the wiring information wrong. I thought that it went from one light and on to the next etc until the last one but without stripping the lights I am not sure. They weren't fitted by myself I am just going from memory when I lined and insulated the ceiling. The cables are in the roof space and there isn't access now.

                          As for the temperature, I can go into the workshop and the lights work fine, come out after an hour or so for a brew then when I go back in I can get the problem. It is the complete light fitting ( Both Tubes ) that don't work. Not even a flicker as if they are trying to come on. Flick the switch on and off a few times or even come back later and they work fine.

                          As I say it can be totally random as to which fitting fails. The supply in the workshop is from the house approximately 25 feet away and supplied through 16mm buried cable to a consumer unit in the workshop. A 10 mm cable then carries on to another outbuilding which has its own lighting and consumer unit and gives no issues at all.

                          I have noticed that the light fittings give off a steady ticking sound for a while when they are switched on for 5 / 10 mins or so. I wasn't sure if it was them just warming up or something ?????

                          I have had the wiring checked when the replacement consumer unit and a separate breaker were fitted for the workshop supply as per a previous thread of mine. It is only since the light fittings were swapped for the new ones approx 18 months ago that the issue has arrived.

                          It is more the nagging inconvenience than anything else. I had always assumed that it was just down to the quality of the light fittings but it happened yesterday so thought I would throw it out there.

                          I will get somebody in to check them incase there is a fault on them somehow.

                          Many thanks

                          #412544
                          Roger Hart
                          Participant
                            @rogerhart88496

                            Time to dredge up this topic?

                            Now repainting the workshop and looking to replace the 6 foot 85Watt fluorescent tube with some sort of led fitting. There are what look to be led striplights about 4 to 5 foot long but it looks to need two to get up to or over the old 85Watts. I am just a bit concerrned that 'led watts' do not amount to 'proper fluorescent tube watts'.

                            Workshop is only 2.5metres by 3.5 metres with normal height ceiling. Any advice?

                            #412553
                            Colin Whittaker
                            Participant
                              @colinwhittaker20544

                              Roger,

                              LED watts seem to be twice as bright as fluorescent watts, at least for normal bulb lights. I think it also holds for tubes.

                              An alternative cheap and efficient light source is the mini 220V LED flood lights. I've used a series of 10W LED floods for dazzling effect.

                              Colin

                              #412554
                              Frances IoM
                              Participant
                                @francesiom58905

                                600 x 600 mm 35W panels mounted within surface mounting “boxes” – the driver fits on top of the panel in the box with the light forming the base and access via a removable side panel (available from most electrical trade dealers eg TLC , City Electrical) – choose daylight (cool blue if you use the workshop mostly in day – warm (less blue) for evening as blue light may make sleep more difficult – if you are comfortable adding a RF remote switch in the box you can control individual lights without any rewiring – the original switch will switch off all – I use this to add panels over individual machines – ideally you want light coming over left shoulder (assuming right handed)

                                Edited By Frances IoM on 04/06/2019 14:28:11

                                #412555
                                Tim Stevens
                                Participant
                                  @timstevens64731

                                  LEDs are much more efficient at producing light, so LED watts are the makers 'guess' at the light output, and not at all the consumption of power. Usually.

                                  So, you should find that the standard versions offered as tube replacements are a bit brighter – mine are. Just be sure that you choose the colour balance which suits you best – I prefer Daylight or cool white, others tend towards the warm white which is closer to filament-lamp colours.

                                  Cheers, Tim

                                  #412558
                                  Harry Wilkes
                                  Participant
                                    @harrywilkes58467

                                    I replaced two of my flo tubes which were several years old and the light output had deteriorated with two led lights and what a difference they made I had not realised how poor my flo lights were

                                    H

                                    #412565
                                    not done it yet
                                    Participant
                                      @notdoneityet

                                      You do realise that these flourescent tubes contain mercury? See the current ‘quicksilver’ thread! smiley

                                      #412626
                                      Dave Halford
                                      Participant
                                        @davehalford22513

                                        Leds I have bought were Watts consumed with the light output rated in lumens.

                                        #412794
                                        Nick Hulme
                                        Participant
                                          @nickhulme30114

                                          I had double fluorescent tubes fittings throughout my garage and singles in my workshop, the LED replacement tubes give better working light than the fluorescents ever did.
                                          I chose LED replacement tubes and rewiring the fittings to eliminate the ballasts, part of my reasoning for this route is that the parts which will eventually fail are an easy user replacement, whereas dedicated LED fittings commonly require replacement of the full lighting unit when they fail.

                                          #412806
                                          duncan webster 1
                                          Participant
                                            @duncanwebster1

                                            I'm switching over to LED tubes as the fluorescents age. One of my fittings is at least 50 years old and has no starter as such. It always either comes on pretty much straight away, or if it's really cold just glows until I give the tube a rub. Can this be converted to take LED tube, or is it time for it to meet it's maker?

                                            #412810
                                            JohnF
                                            Participant
                                              @johnf59703

                                              Dave I fitted these in my workshop a couple of years ago to replace 2 ancient 8ft fluorescent fittings, there is also a relatively new 4 ft florescent over the bench so did not reface that.

                                              Much brighter than the old 8ft ones and more economical

                                              John

                                              img_1641.jpg