VFD problem

VFD problem

Home Forums General Questions VFD problem

Viewing 20 posts - 1 through 20 (of 20 total)
  • Author
    Posts
  • #339322
    Andy Sproule
    Participant
      @andysproule22368

      Hi was using mill today and it just stopped while doing a fairly heavy cut.There is power going to the VFD but it is not coming on.I have pressed the reset and the run button but no joy is there a trip or any such like that I should look for inside this VFD?img_2961.jpg

      #25792
      Andy Sproule
      Participant
        @andysproule22368
        #339325
        Ian P
        Participant
          @ianp

          Its probably easier for you to look in the manual as no one here is likely to know the model number.

          Doubtful if you will see anything amiss if you open the casing.

          Are there any error codes showing?

          Was there a pop and a bang, or maybe a burning smell?

          Ian P

          #339333
          Andy Sproule
          Participant
            @andysproule22368

            Don't have a manual.No pop,bang or burning smell.No light up on the screen.

            #339334
            David Jupp
            Participant
              @davidjupp51506

              Maybe try removing power for a few minutes then re-connecting. It's a long shot, but low cost to try. It's usually possible to find manuals on-line somewhere if you have make and model number.

              #339336
              David George 1
              Participant
                @davidgeorge1

                It sounds like a fuse or overload but could be anything. Check any fuses after isolating the supply. Try and find a manual on line at least give us a clue with a make and model No.

                David

                #339342
                Muzzer
                Participant
                  @muzzer

                  …first check the fuse in the plug. You may find it was a 5A one or something silly.

                  Murray

                  #339348
                  Andy Sproule
                  Participant
                    @andysproule22368

                    Its not the plug fuse.The VFD is an Ls sv008ic5-1f have down loaded and am reading through now.

                    #339364
                    Andy Sproule
                    Participant
                      @andysproule22368

                      The VFD clicks for a second every 45 seconds it partially lights up the fans give a kick and then off again.

                      #339368
                      Ian P
                      Participant
                        @ianp

                        If the symptoms you see are not mentions in the manual and there are no error codes showing then I suggest you disconnect all the control wiring from the VFD, leaving only the motor and power in connected. Then carry out a factory reset and return the VFD to an 'as new' state.

                        Input the basic motor details and see if you can control it using the VFDs own buttons. If it is still faulty then my diagnosis would be that it is a real faulty that probably needs a board level repair.

                        Ian P

                        #339373
                        Muzzer
                        Participant
                          @muzzer

                          Sounds as if it's popped to me. Twitching periodically sounds like a pretty serious internal issue. If so, bin it and buy another, as repair won't be economical.

                          If you discover a blown fuse somewhere inside, bear in mind that they are fitted to prevent fire or hazard in the event of a circuit failure. Replacing the fuse is unlikely to repair the fault but if you use the wrong sort, you could create a risk of fire or injury.

                          Murray

                          #339449
                          OuBallie
                          Participant
                            @ouballie

                            Had that problem using the drilling machine doing heavy low speed work.

                            Waited 3-5min and all back to normal.

                            Ditto a second time.

                            Just switched everything off on both occasions.

                            That was months ago and not repeated since.

                            Wonder if there was any feedback from motor to the VFD of overheating?

                            Geoff – We need Noah's Ark.

                            #339453
                            Ian P
                            Participant
                              @ianp
                              Posted by OuBallie on 02/02/2018 11:37:31:

                              Wonder if there was any feedback from motor to the VFD of overheating?

                              Geoff – We need Noah's Ark.

                              More likely a temperature sensor in the VFD itself.

                              I have a Huanwang, which I have modified by disconnecting its internal fan and rewiring it via a thermostat attached to the VFD heatsink. The fan only runs once in a blue moon, or more accurately only when there has been a prolonged period of heavy load. Even then the motor is barely warm and the fan stops within 30 seconds of me stopping the motor.

                              In spite of its low price I suspect the Huanwang has a slightly oversize internal heatsink compared to many of the physically smaller VFDs.

                              Ian P

                              #339454
                              Andy Sproule
                              Participant
                                @andysproule22368

                                Thanks for all the replies guys I think she is cooked.

                                #339457
                                John Chapman 5
                                Participant
                                  @johnchapman5

                                  The unit is in a state of trip, try disconnecting the motor then power it up. If it powers up OK it is the motor at fault if it don’t it is the VFD .

                                  John

                                  #339461
                                  Nick Hulme
                                  Participant
                                    @nickhulme30114

                                    Until you try to run the load a VFD doesn't output anything and will look normal whether there is a short or open circuit on the output.

                                    If you think it's broken you won't lose anything by taking a look inside, start with where the power feeds in and look for anything unusual.

                                    #339469
                                    John Rudd
                                    Participant
                                      @johnrudd16576

                                      My experience with IMO /Teco inverters, they will display an error if there is a short or open circuit in the ouput stage…This is down to the way the inverter micro monitors over voltage/current oveload conditions, there is also a bus voltage monitor for under/overvolts conditions….Other error messages include temperature sensing of the heatsink.

                                      Depending in the size of the inverter, discrete devices may be used or a dedicated 3 ph " chip" may be used for the high current stages…where discrete devices are used, repair is a lot easier…

                                      #339483
                                      OuBallie
                                      Participant
                                        @ouballie

                                        Thanks Ian P.

                                        Sounds more like it.

                                        The motor was getting somewhat hot, but even switching the belt to different pulley grooves to get the motor fan speed up, but spindle speed not, didn't help much as the second switch off proved.

                                        Next time will have to sort out a method of forced draught into the VFD enclosure.

                                        The drilling was when I made a holder for my 5C collets using a step drill & 3mm ally sheet.

                                        Geoff – Heating via electric oil heaters and electric blanket, the latter utter bliss.

                                        #339484
                                        Nick Hulme
                                        Participant
                                          @nickhulme30114
                                          Posted by John Rudd on 02/02/2018 13:46:04:

                                          My experience with IMO /Teco inverters,

                                          Cool, Siemens and ABB don't fault until running

                                          #339502
                                          John Rudd
                                          Participant
                                            @johnrudd16576

                                            Nick,

                                            I ought to have elaborated, the Teco/IMO inverters fault when the Run button is pressed, except for the Bus voltage faults….the drive can be static and will display bus faults, either volts high or low…preventing a start.

                                          Viewing 20 posts - 1 through 20 (of 20 total)
                                          • Please log in to reply to this topic. Registering is free and easy using the links on the menu at the top of this page.