  • #350898
    Brian H
    Participant
      @brianh50089

      I need to provide 3 phase electricity from a single phase supply to one motor of 1/2 HP that has a dual voltage on the motor plate which states that it is an AEI motor 220/250v to 380/440v at 1.6/ 0.9a.

      I think I've found the correct converter to do this but the whole subject seems to be full of questions.e.g. some converters supply 240V per phase, does that mean it's a 220v to 720v converter?

      I think I need a 240v to 440v converter, but I don't need infinitely variable speed as the belts and pulleys on the machine will give the speeds that correspond to the ones on the machines data plate.

      Can someone provide a simple explanation?

      Brian

      Brian

      #25946
      Brian H
      Participant
        @brianh50089
        #350902
        Speedy Builder5
        Participant
          @speedybuilder5

          Do you really need 3 phase? It may be cheaper to replace the motor. If you are not used to 3 phase, bear in mind it is LETHAL if you do not RESPECT it. 240volts is bad enough, but 440 volts…. You will see lots of posts about 3 phase on this site – I wonder if it is legal to permanently wire in motors etc ??
          BobH

          #350904
          John Rudd
          Participant
            @johnrudd16576

            Brian,

            There are two simple options.

            You can swap the motor out for a single phase version, if you can find a drop in replacement, or, rewire the motor connecting the windings in Delta fashion ( google star-delta wiring) and buy a 1hp inverter 240 v ac in and 3 ph out…

            There are plenty of suppliers, Engineers Mate, Drives Direct…( I've used both suppliers…usual disclaimer…)

            Edited By John Rudd on 20/04/2018 20:51:36

            #350905
            Les Jones 1
            Participant
              @lesjones1

              The most common VFDs are supplied from 240 volts single phase and supply a three phase output that is 240 volts phase to phase. You can get more expensive ones that will supply 415 volts phase to phase so that you can use a motor that cannot be configured for 240 volts phase to phase. The motor you have can be configured in a delta connection for 240 volts phase to phase or in star connection for use with 415 volts phase to phase.

              Les.

              #350906
              Brian H
              Participant
                @brianh50089

                Thanks for the reply Bob. Unfortunately the motor is a special flange mounted one so may be difficult to replace and I prefer the smoothness of 3ph

                I am very familiar with 3 phase as I used to run a machine from a static converter and then moved house to find three 400A fuses coming through the floor in the meter cupboard! To say I was overjoyed was an understatement!

                I'm not an electrician but always prefered working 3 ph rather that 1 ph. I'm VERY respectful of electricity and so take no chances.

                Brian

                Edited By BDH on 20/04/2018 21:00:33

                #350908
                Philip D
                Participant
                  @philipd

                  Brian,

                  If you have 3phase to the house why run an inverter ???

                  Philip

                   

                  Edited By Philip Devonport on 20/04/2018 20:59:23

                  #350909
                  Brian H
                  Participant
                    @brianh50089

                    Many thanks for the reply Les, which sets my mind at ease. Your info matches something I have read and the instructions that come with the inverter I am looking at show the two types of connection needed.

                    I definitely owe you one.

                    Brian

                    #350911
                    Brian H
                    Participant
                      @brianh50089

                      Philip, I should have said that I've moved house again and sadly, there is only a single phase supply here.

                      Brian

                      #350912
                      Philip D
                      Participant
                        @philipd

                        Brian,

                        That would explain it. Just be aware you need to keep the inverter out of tight spaces for airflow and pretty clean as they do attract dust/debris.

                        Philip

                        #350924
                        Bazyle
                        Participant
                          @bazyle

                          You said in another post that you were only a few miles from Drives Direct. Just take the motor off and take it along to them when you buy the inverter. Probably best to arrange an appointment first. Your motor is the type that can be converted to Delta.

                          #350925
                          John Rudd
                          Participant
                            @johnrudd16576
                            Posted by Bazyle on 20/04/2018 22:28:53:

                            You said in another post that you were only a few miles from Drives Direct. Just take the motor off and take it along to them when you buy the inverter. Probably best to arrange an appointment first. Your motor is the type that can be converted to Delta.

                            Should you choose to go to Drives Direct, I've always found Dave very helpful and will assist any way he can…

                            Edited By John Rudd on 20/04/2018 22:37:09

                            #350946
                            Brian H
                            Participant
                              @brianh50089
                              #351114
                              John Rutzen
                              Participant
                                @johnrutzen76569

                                Hi , buy the MAP publications book on Electric Motors. There is a chapter that tells you how to run 3 phase motors on single phase. I have had my lathe running like this for the last 25 years with no problems.

                                #351850
                                STK2008
                                Participant
                                  @stk2008

                                  Just thinking out aloud here probably make my self look silly but I am used to that 😛

                                  How does home insurance stand on 440V etc.

                                  If you have home insurance it might be worth just looking through it to make sure they are ok with 440V machines lets be honest theres not many people who have 440V items in there home they might not be willing to insure it as its realy classed as industrial?.

                                  #351857
                                  John Rutzen
                                  Participant
                                    @johnrutzen76569

                                    If you change the motor from star to delta connection as Jim Cox explains in his book on Electric Motors then the motor is running on 240 volts.

                                    #351867
                                    Vic
                                    Participant
                                      @vic

                                      I changed the wiring from star to delta on my old milling machine and connected a suitable capacitor across two of the windings and ran it on single phase.

                                      I believe this topic is covered in the workshop practice series on electric motors. You only get about 80% of the rated power but I never had a problem using the machine.

                                      Edited By Vic on 27/04/2018 15:00:16

                                      #351910
                                      Anonymous
                                        Posted by STK2008 on 27/04/2018 12:04:44:

                                        How does home insurance stand on 440V etc.

                                        If you have home insurance it might be worth just looking through it to make sure they are ok with 440V machines lets be honest theres not many people who have 440V items in there home they might not be willing to insure it as its realy classed as industrial?.

                                        In my experience home insurance doesn't want to know about any machine tools. One, they rarely insure anything of significant value within garages or sheds. Two, they're utterly clueless about what a lathe or milling machine is, so there's no way they will insure it. As it happens almost all my machines run on 415V 3-phase. They, and my part built engines and material, are insured via Walter Midgeley, separate from my house insurance. The issue of single or 3-phase didn't come into the quote, simply estimated value.

                                        Andrew

                                        #352333
                                        STK2008
                                        Participant
                                          @stk2008

                                          Andrew Johnston

                                          ah ok

                                          Also thanks for info as I am looking at getting insurance for the machines etc in my garage shall look up Walter Midgeley.

                                          #352345
                                          John Haine
                                          Participant
                                            @johnhaine32865

                                            The UK 3 phase distribution side supply is 230v phase to neutral, 415 phase to phase. Arguably therefore it is no different in terms of insurance hazard from standard single phase mains.

                                            #352348
                                            Brian H
                                            Participant
                                              @brianh50089

                                              Many thanks to all for the input; I decided to go with the inverter from Drives Direct which is a 10 minute drive from me and they are VERY helpful.

                                              I wasn't too sure if I needed any extra components or exactly which wires went where but they have a scheme where you send them pictures of your machine motor connections etc and they provide instructions on how to wire it, and all for £25.00, a lot cheaper than an electrician.

                                              Brian

                                              #352351
                                              Dave Martin
                                              Participant
                                                @davemartin29320
                                                Posted by STK2008 on 01/05/2018 11:55:25:

                                                ….shall look up Walter Midgeley.

                                                Just to make it easier to find if you're searching on-line, I've no connection but their name is Walker Midgley

                                                #352359
                                                Emgee
                                                Participant
                                                  @emgee

                                                  I'm sure if you posted pictures of your motor connection box, motor plate and starter you would receive FOC information required to correctly connect your motor.

                                                  Emgee

                                                  #352371
                                                  Brian H
                                                  Participant
                                                    @brianh50089

                                                    Many thanks Emgee but I'm ok with the wiring to the motor, even changing from star to delta but it's the connections to the inverter that are the problem.

                                                    Brian

                                                  Viewing 24 posts - 1 through 24 (of 24 total)